Motor Calculations: From FLA to the Licensing Exam
A topic that shows up on journey-level and master licensing exams.
Motor calculations show up on most licensing exams. Learn the FLA → conductor → OCP → disconnect path until it's automatic.
0% complete · 0/5 lessons · 0/5 quizzes passed
What you'll learn
- Module 1Full-Load Amperes (FLA)Table 430.247 / 248 / 249 / 250. Never use nameplate for conductor sizing.1 lessons · 4 questions
- Module 2Branch Circuit Conductors — the 125% Rule430.22: conductors sized at 125% of table FLA.1 lessons · 4 questions
- Module 3Motor Overcurrent Protection (OCP)430.52 and Table 430.52 — inverse-time 250%, dual-element fuse 175%, instantaneous trip 800%.1 lessons · 4 questions
- Module 4Motor Disconnect and Controller430.102 disconnect requirements; controller must break locked-rotor current.1 lessons · 3 questions
- Module 5Full Motor Circuit Calculation — Exam DrillHP + voltage → FLA → conductor → OCP → disconnect, until it's automatic.1 lessons · 4 questions